VOLTAGE STABILITY INDICATOR AT THE PROXIMITY OF THE VOLTAGE COLLAPSE POINT AND ITS IMPLICATION ON MARGIN

GURPREET SINGH DEOL1, SHAILY SAO2*, HARMANDEEP SINGH3, VIKAS GUPTA4
1Electrical Engineering Department Punjab Technical University
2Electrical Engineering Department Punjab Technical University
3Electrical Engineering Department Punjab Technical University
4Electrical Engineering Department Punjab Technical University
* Corresponding Author : shailysao@gmail.com

Received : 30-11-2011     Accepted : 12-12-2011     Published : 14-12-2011
Volume : 2     Issue : 2       Pages : 54 - 58
J Electron Electr Eng 2.2 (2011):54-58

Cite - MLA : GURPREET SINGH DEOL, et al "VOLTAGE STABILITY INDICATOR AT THE PROXIMITY OF THE VOLTAGE COLLAPSE POINT AND ITS IMPLICATION ON MARGIN." Journal of Electronic and Electrical Engineering 2.2 (2011):54-58.

Cite - APA : GURPREET SINGH DEOL, SHAILY SAO, HARMANDEEP SINGH, VIKAS GUPTA (2011). VOLTAGE STABILITY INDICATOR AT THE PROXIMITY OF THE VOLTAGE COLLAPSE POINT AND ITS IMPLICATION ON MARGIN. Journal of Electronic and Electrical Engineering, 2 (2), 54-58.

Cite - Chicago : GURPREET SINGH DEOL, SHAILY SAO, HARMANDEEP SINGH, and VIKAS GUPTA "VOLTAGE STABILITY INDICATOR AT THE PROXIMITY OF THE VOLTAGE COLLAPSE POINT AND ITS IMPLICATION ON MARGIN." Journal of Electronic and Electrical Engineering 2, no. 2 (2011):54-58.

Copyright : © 2011, GURPREET SINGH DEOL, et al, Published by Bioinfo Publications. This is an open-access article distributed under the terms of the Creative Commons Attribution License, which permits unrestricted use, distribution and reproduction in any medium, provided the original author and source are credited.

Abstract

Maximum power transfer and optimal reactive power at voltage stability limit is the major problem. In power system, engineers faced with problem of variable load ranging from minimum to maximum at or near a constant value of voltage. A power system must be planned and operated in such a manner so as it gives good quality of reliable supply. Power system must be planned, designed installed and operated in such a manner so as to avoid voltage instability and voltage collapse. When the inductive load is increased the reactive power absorption is increased and hence voltage drop in transmission lines is increased and receiving end voltage is decreased. Voltage drop in transmission line depends upon the reactive power. Power transfer and receiving end voltage can be enhanced by using shunt compensation in order to increase the load. This paper looks in to a power flow program in MATLAB environment. Thus it is a graphical method to find out the magnitude of power transfer and receiving end voltage at steady state voltage stability limit and optimum value of power transfer and receiving voltage when the system is at stable state.

Keywords

Power Transfer capability, Receiving End Voltage, Voltage Stability Margin, Voltage Stability

Introduction

Voltage stability problems have received increased attention over the last few years. Since power systems are operated under maximum loading condition the ability to maintain voltage stability has become a major problem and good measures to improve the reactive power and voltage level control are required. If effective control actions are not appropriately implemented, successive load increases may drive a system to an unstable state, at which abnormal operating conditions can be identified. [17] , the following formal definitions of terms related to voltage collapse are given in reference [10] :
• Voltage stability refers to the ability of a power system to maintain steady voltages at all buses in the system after being subjected to a disturbance from a given initial operating condition.
• Voltage Collapse is the process by which voltage instability leads to loss of voltage in a significant part of the system.
• Large-Disturbance Voltage Stability refers to the system’s ability to maintain steady voltages following large disturbances such as system faults, loss of generation, or circuit contingencies. This ability is determined by the system and load characteristics, and the interactions of both continuous and discrete controls and protections.
• Small-Disturbance Voltage Stability refers to the system’s ability to maintain steady voltages when subjected to small perturbations such as incremental changes in system load. This form of stability is influenced by the characteristics of loads, continuous controls, and discrete controls at a given instant of time.
A system becomes unstable when a disturbance (load increase or other system change) voltage to drop quickly or drift downward, and operators and automatic system control fail to improve the voltage level [17] .

Methodology

Firstly the expression of receiving end voltage VR and complex power S for two bus system is derived
Real Power Flow



And Reactive Power Flow





The expression (3) shows the magnitude of receiving end voltage in terms of A0 and B0, where A0 = A, B0= B, the A, B, C, D parameter of the system.
The expression of (3) gives the magnitude of receiving end voltage having two values, upper voltage and lower voltage. For stable operation of expression (3) is positive. When the system load increases and approaches to voltage collapse point both the higher and lower voltages approaches to same value, and is called critical voltage. For determining the critical value of complex power S





Now using expressions (1), (2), (3) and (4) three program are built in MATLAB environment.

A. Modified A, B, C, D Parameter with Shunt Compensation
A, B, C, D parameter are used to represent transmission line. It depends upon the system parameters. When shunt reactive support is add to the system, the values of A, B, C, D parameter are changed, therefore called modified A, B, C, D parameter and represented by Am, Bm, Cm and Dm.

At no load condition current at receiving end is zero as given in [Fig-2] .















In matrix form,



Now the modified parameter,





For Phase constant β=90°







Where

Similarly,





Here is the shunt compensation.

B. An Indicator of Voltage Stability and its Implication of Voltage Stability Margin
Considering a generator bus connected to a load bus through a transmission line having series admittance YL and shunt admittance YS.
Line current is given by





And the system admittance matrix



Where V, IR, SR and E, IS, SS are complex voltages, current and power at receiving end and sending end respectively.
The load current IR is given by



And from (5),



A comparison between (6) and (7) gives,





Where δ is the angular difference between V and E and





Noting that V0 is kept constant by keeping the sending end voltage constant,



And



The Jacobian corresponding to these power flow equation is given by





Assuming the singularity of Jacobian, at voltage stability limit, i.e.,



Expression (14) determines the voltage stability limit where the point of voltage instability coincides with the singularity of Jacobian matrix of the load flow.
Here from the equation (14)





Again from (8)



The above equation can further be simplified by taking the complex conjugate on both sides, and dividing by as



Where



The expression (17) gives the criteria of voltage stability of the assumed line model. In other words, for a system as described, to retain its voltage stability, magnitude of expression must be less than unity. Thus is the voltage stability indicator.
Voltage Stability Margin (Mv) is defined as



MV represent the margin of voltage collapse for a system.
For the practical analysis to verify the theoretical concept a single circuit of 60-Hz transmission line is 370 Km (230 mi) long is taken. The conductors are Rook with flat horizontal spacing and 7.25 m (23.8 ft) between conductors. The load on the line is 125 MW at 215 KV with 100% power factor.

Result and Discussion

The stable operation is possible when voltage stability margin is positive and lies between 0 and 100%. In [Fig-4] to [Fig-10] , gives different curves of load voltage, power transfer verses voltage stability margin. A voltage regulator of -10% is assumed. The dotted line area represents voltage stability margins under this condition.
These curves give following result:
It can be observed from [Fig-4] that a high range of voltage stability margin from 91% to 95% obtain for the proposed range of allowable voltage regulation of -10%. However power transmission is very low it is only 0.5 p.u. to 0.65 p.u. receiving end voltage is 0.65 p.u. With the increase of power transfer, receiving end voltage drops with decrease in voltage stability margin. In [Fig-5] , with shunt reactive support, though the voltage stability zone is widened when the magnitude of voltage stability margin is reduced from 87% to 91% whereas the magnitude of power transfer is increased from 0. 61 p.u. to 0.72 p.u. and the magnitude of receiving end voltage is improved to 0.7 p.u. Similarly with further increase of shunt compensation as shown in [Fig-6] , [Fig-7] , [Fig-8] power transfer and receiving end voltage is increased and voltage stability margin is reduced. With further increase in shunt capacitor value as shown in [Fig-9] though the terminal voltage increases, voltage stability margin becomes remarkably narrow for the condition of -10% voltage regulations in receiving end voltage. The power transfer increases marginally and the state of operation corresponding to this voltage stability margin is closed to steady state voltage stability limit 1.2 p.u.
Further increase of shunt reactive support at load bus corresponding to [Fig-10] enhances the receiving end voltage and operation with positive voltage stability margin is not possible for the proposed range of regulation.

A. Comparison of power transfer capability for different values of shunt reactive compensation
Power transfer capability increases as the shunt reactive compensation are added to the system. When there is no shunt compensation power transfer capability is 0.7p.u. and when the value of Ycap = 0.7 it becomes 1.3 p.u.

B. Comparison of Receiving End Voltage for Different Values of Shunt Reactive Compensation
Receiving end voltage also increases as the shunt reactive compensation increases at the load bus as describes in [Fig-12] . It shows how receiving end voltage is increased from no any compensation to high value (70 μF) of shunt compensation.

Conclusion

To transmit power to transmission line within stable voltage limits, the magnitude of is less than unity during maximum power transfer and any overloading of the system beyond this stage leads to voltage instability.
It is further observed that for a longitudinal power transmission system, where the voltage regulation is restricted -10% only, the magnitude of power transfer and receiving end voltage can be enhanced by shunt capacitive support at load end. However the voltage stability margin reduces with the shunt capacitive support for a fixed amount of allowable voltage regulation.
The approximate optimum range of capacitive support can be assessed graphically for a reasonable safe range of voltage regulation and power transfer for this line model. Any lower or higher values of shunt compensation may cause voltage instability violating the condition of ±10% transmission voltage regulation.

References

[1] Chakrabarti A., Kothari D.P. and Mukhopadhyay (2000) Performance, Operation and control of EHV Power Transmission Systems, I st edition, New Delhi Wheeler chapter no 6 pp 132 -141.  
» CrossRef   » Google Scholar   » PubMed   » DOAJ   » CAS   » Scopus  

[2] Kimbark Edward Wilson (2004) Power System Stability Volume-I, IInd edition A John Wiley & Sons, Inc. Publisher, New York. chapter no 1 page no 11-12.  
» CrossRef   » Google Scholar   » PubMed   » DOAJ   » CAS   » Scopus  

[3] Kundur P (2009) Power System Stability and Control Ist ed I McGraw-Hill Publisher, New York. chapter no 14 page no 960-965.  
» CrossRef   » Google Scholar   » PubMed   » DOAJ   » CAS   » Scopus  

[4] Rao S.S. (2009) Swichgear Protection and Power Systems, 13th.edition Khanna Publisher Delhi. chapter no 45 C page no 959-962.  
» CrossRef   » Google Scholar   » PubMed   » DOAJ   » CAS   » Scopus  

[5] Stevenson William D (1982) Element of Power System Analysis IVth. Edition McGraw Hill. chapter no 5 page no 101-113.  
» CrossRef   » Google Scholar   » PubMed   » DOAJ   » CAS   » Scopus  

[6] Wadhawa C.L. (2009) Electrical Power System Vth Edition New Age International (P) Limited Publishers, New Delhi. chapter no 10 page no 226-228.  
» CrossRef   » Google Scholar   » PubMed   » DOAJ   » CAS   » Scopus  

[7] Sayonsom Chanda and Bappa Das (2011) IEEE transaction on power System volume. no. 978 page 4244-7882.  
» CrossRef   » Google Scholar   » PubMed   » DOAJ   » CAS   » Scopus  

[8] Haque M.H. (2002) IEEE transaction on power System volume no.2 page no 0272-1724.  
» CrossRef   » Google Scholar   » PubMed   » DOAJ   » CAS   » Scopus  

[9] Garng M Huang, Liang Zhao and Xuefeng Song (2002) IEEE transaction on power System pp 7803-7322.  
» CrossRef   » Google Scholar   » PubMed   » DOAJ   » CAS   » Scopus  

[10] Kundur P, John Ajjarapu, Andersson P.V., Bose G.A, ClaudioCanizaros, Nikos H, Hill D, Slankovic A, Taylor C, Van Cutsem T, Vijay Vittal (2004) IEEE Transection on Power System volume 19, no. 2 page no 1387- 1400.  
» CrossRef   » Google Scholar   » PubMed   » DOAJ   » CAS   » Scopus  

[11] Mark N Nwohu (2009) Journal of Sciences, 1583-0233.  
» CrossRef   » Google Scholar   » PubMed   » DOAJ   » CAS   » Scopus  

[12] Phadke A.R., Manoj Fozdar and Niazi K.R. (2008) “A New Technique for on-line Monitoring of Voltage Stability Margin Using Local Signals”, Fifteenth National Power Systems Conference (NPSC), IIT Bombay page no 488- 492  
» CrossRef   » Google Scholar   » PubMed   » DOAJ   » CAS   » Scopus  

[13] Chepuri S Rao and Attri K.S. (1993) IEEE Tencon page no 322-325.  
» CrossRef   » Google Scholar   » PubMed   » DOAJ   » CAS   » Scopus  

[14] Mustafa Turan, Serdar Basar Demircioglu and Mehmet Ali Yalcin (2006) Journal of Applied Science 6(13) 2809-2812.  
» CrossRef   » Google Scholar   » PubMed   » DOAJ   » CAS   » Scopus  

[15] Andrzej Wiszniewski (2007) IEEE Transaction on Power Delivery volume no 22 no. 3.page no 1367-1371  
» CrossRef   » Google Scholar   » PubMed   » DOAJ   » CAS   » Scopus  

[16] Yome A. Sode, Mithulananthan N (2006) IEEE transaction on power System volume no. 1 page 4244-049.  
» CrossRef   » Google Scholar   » PubMed   » DOAJ   » CAS   » Scopus  

[17] Renuga Verayiah and Izham Zainal Abidin (2008) “A Study on Static Voltage Collapse Proximity Indicators”2nd IEEE International Conference on Power and Energy, Johor Baharu, Malaysia page. no. 4244-2405.  
» CrossRef   » Google Scholar   » PubMed   » DOAJ   » CAS   » Scopus  

[18] Yajing Gao Ming, Zhao Gengyin, Li Yuekui Huang, Limin Xiao and Rui Li (2005) “Monte Carlo Simulation Based Available Transmission Capability Calculation” paper presented on IEEE/PES Transmission and Distribution Conference & Exhibition. Dalian China.  
» CrossRef   » Google Scholar   » PubMed   » DOAJ   » CAS   » Scopus  

Images
Fig. 1- Two bus system in transmission line
Fig. 2- network of transmission lines in terms of A, B, C D parameter at no load.
Fig. 3- Equivalent Circuit of [Fig-2]
Fig. 4- Load voltage and power transfer versus margin. voltage stability margin without any compensation.
Fig. 5- Load voltage and power transfer versus voltage stability margin with 10% compensation
Fig. 6- Load voltage and power transfer versus voltage stability margin with 20% compensation
Fig. 7- Load voltage and power transfer versus voltage stability margin with 30% compensation
Fig. 8- Load voltage and power transfer versus voltage stability margin with 40% compensation
Fig. 9- Load voltage and power transfer versus voltage stability margin with 60% compensation
Fig. 10- Load voltage and power transfer versus voltage stability margin with 70% compensation.
Fig. 11- Comparison of power transfer capability for different value of shunt compensation.
Fig. 12- Comparison of receiving end voltage at different value of shunt reactive compensation